Skip to content

LVL Beam Guide: Sizes, Strength, and LVL vs Steel Beams

What an LVL beam is, common sizes, published 2.0E design values, and how LVL compares with a steel W8x10 for stiffness, weight and headroom in house framing.
Source: AISC Shapes Database v16.0Imperial & metric
LVL Beam Guide: Sizes, Strength, and LVL vs Steel Beams

An LVL beam is a structural wood beam made from thin wood veneers glued together with the grain of every layer running the length of the beam. LVL stands for laminated veneer lumber, and it is used in houses wherever sawn lumber is not strong or straight enough: garage door headers, beams that replace a load-bearing wall, ridge beams and floor girders.

This guide explains how LVL is made, the common sizes, the published design values for one widely used grade, how it compares with a steel beam of the same depth, and the installation rules that trip people up. Figures were checked against the manufacturer’s documents on October 30, 2026.

How an LVL Beam Is Made

Logs are peeled into thin sheets of veneer, dried, coated with adhesive and laid up into a long billet that is pressed and heat-cured. The billet is then ripped into beams of the required depth. Because the veneers are thin and staggered, a knot or split in one layer is backed up by sound wood in the layers around it. That is why LVL has higher and far more consistent design values than a sawn 2×12 cut from the same tree.

The ICC-ES evaluation report ESR-1387 (revised July 2026) for Weyerhaeuser’s Microllam LVL describes it as wood veneers laminated with an exterior-type structural adhesive, with all veneers oriented with the grain parallel to the length of the member. The same report lists depths from 2.50 to 48 inches and lengths up to 80 feet, and states that the products comply with ASTM D5456, the standard for structural composite lumber.

Three LVL plies, each 1-3/4 inches wide, nailed side by side to make a 5-1/4 inch wide beam. A close-up of one ply shows thin veneer layers stacked vertically, all with grain running along the length of the beam. A second sketch compares it with a steel wide flange beam of similar depth. 3-ply LVL beam 3 x 1-3/4 in = 5-1/4 in veneers glued face to face steel wide flange material kept in the flanges far from the center depth
End view of a three-ply LVL beam next to a steel wide flange of similar depth. LVL is a solid rectangle; the steel shape puts its material in the flanges. Not to scale.

Common LVL Beam Sizes

LVL is sold mostly in a single ply width of 1-3/4 inches. Wider beams are built by fastening two, three or four plies together, giving 3-1/2, 5-1/4 and 7 inch widths that match 2×4 and 2×6 wall framing. Depths follow the wood I-joist depths so beams and joists sit flush. TB-508 covers the shallow 5-1/2 and 7-1/4 inch depths used for studs and short headers, and the Microllam LVL beams page lists separate design guides for 22 and 24 inch deep 2.0E beams. Not every depth is stocked in every region, so check with a local lumber yard before you design around one.

If you are matching an LVL beam to floor joists, our wood I-joist size chart lists the standard joist depths.

What “2.0E” means

LVL is graded by stiffness. A 2.0E beam has a modulus of elasticity (E) of 2.0 million psi. Lower grades such as 1.9E or 1.75E exist and some brands sell them as headers. Span tables are grade specific, so a 1.9E beam cannot be dropped into a design that called for 2.0E without a recheck.

Published Design Values for 2.0E LVL

Weyerhaeuser’s technical bulletin TB-508 (May 2025) lists these allowable design values for 2.0E Microllam LVL at 100% load duration. Other brands publish their own values, which can differ.

Property (beam orientation)2.0E Microllam LVL
Modulus of elasticity, E2.0 x 106 psi
Bending, Fb (12 in depth)2,600 psi
Shear, Fv285 psi
Compression perpendicular to grain, Fc⊥750 psi
Compression parallel to grain, Fc∥2,510 psi

The same bulletin gives section values for single 1-3/4 inch plies in the two shallowest depths:

Single ply 2.0E LVLAllowable moment (ft-lb)Allowable shear (lb)Moment of inertia (in⁴)Weight (lb/ft)
1-3/4 x 5-1/2 in2,1251,830242.8
1-3/4 x 7-1/4 in3,5552,410563.7

These are reference values for one product. They do not tell you what a beam can carry over your span, because that depends on the loads, the span, the bearing length, bracing and the deflection limit. A licensed structural engineer, or the manufacturer’s sizing software used by a qualified designer, has to size any LVL beam that carries a wall, floor or roof.

LVL vs Steel Beam

The usual alternative to a deep LVL beam is a steel wide flange. The two behave very differently, and the clearest way to see it is stiffness, which is E multiplied by the moment of inertia I. Stiffness controls how much a beam sags.

BeamDepth (in)Weight (lb/ft)I (in⁴)E (psi)EI (lb-in²)
1 ply 1-3/4 x 7-1/4 LVL7.253.7562,000,000112 million
3 ply 5-1/4 x 7-1/4 LVL7.2511.11682,000,000336 million
W8x10 steel7.891030.829,000,000893 million

LVL values from TB-508 above; W8x10 dimensions from the AISC Shapes Database v16.0, with E = 29,000 ksi for structural steel. At about the same depth and weight per foot, the W8x10 is roughly 2.7 times as stiff as a three-ply 7-1/4 inch LVL beam. That is the main reason steel wins where headroom is tight: it can carry the same load at a shallower depth.

When LVL is the better choice

  • Moderate spans in wood framing. LVL nails, screws and bolts to studs and joists with ordinary carpentry tools and standard joist hangers.
  • Hand installation. Plies can be carried in one at a time and fastened together in place, which matters in a finished basement or a second-floor opening.
  • No welding or drilling steel on site. Connections are carpentry, not fabrication.

When steel is the better choice

  • Flush or shallow beams. When a beam must stay within the ceiling depth, steel’s higher stiffness often makes the difference.
  • Long spans or heavy point loads. Deflection grows fast with span, and steel’s E of 29,000 ksi is about 14 times that of 2.0E LVL.
  • Wet or exposed locations. Standard LVL is meant for dry service; painted or galvanized steel handles damp basements and exterior exposure better.

A middle option is a flitch beam, which sandwiches a steel plate between wood members. For typical steel sizes and the spans they reach, see the steel beam span chart.

Where LVL Beams Are Used

  • Headers over garage doors, patio doors and wide windows. Our guide to headers in construction covers how they carry loads around openings.
  • Flush and dropped beams that replace a load-bearing wall in an open-plan remodel.
  • Girders and basement beams that carry floor joists to posts or columns.
  • Ridge beams in vaulted ceilings, where the beam carries roof load to posts at each end.
  • Tall wall studs and columns. TB-508 states that 1-3/4 x 5-1/2 inch 2.0E LVL studs may be conventionally specified for walls up to 10 feet high, within the limits of the manufacturer’s wall guide.

Installation Rules That Matter

Fastening multiple plies

A multi-ply beam only works as one member if the plies are fastened to the manufacturer’s nailing or bolting schedule. The schedule depends on the number of plies, the depth and whether the load comes from one side. Loads hung off one face, such as joists in hangers, need more fasteners than loads sitting on top.

Bearing length

The ends of the beam must sit on enough post or stud area that the wood is not crushed. With Fc⊥ limited to 750 psi in the table above, a heavily loaded beam can need two or three jack studs or a wide post under each end. The engineer’s drawings should state the minimum bearing at each support.

Holes and notches

Do not cut, notch or drill an LVL beam unless the manufacturer’s allowable-hole chart permits it at that location. Notches at the bottom edge near a support are especially damaging, because that is where shear is highest.

Keep it dry

Store LVL off the ground and covered. Standard LVL is not preservative treated, and long exposure to wet conditions can cause swelling and loss of strength. Beams resting on concrete or masonry normally need a moisture barrier or treated sill between the wood and the concrete.

For basement girders specifically, our basement support beam guide covers the beam choices and the posts that hold them up.

LVL Beam FAQ

Is an LVL beam stronger than a 2×12?

Yes, for the same size. LVL’s published design values are higher than those of common sawn lumber grades, and they are more consistent because defects are spread across many thin veneers.

How far can an LVL beam span?

There is no single answer. The span depends on the load the beam carries, the number of plies, the depth, the grade and the deflection limit. Manufacturers publish load tables and sizing software, but the final size must be checked by a licensed structural engineer or qualified designer.

Can LVL be used outside?

Standard LVL is intended for dry, protected use. For exposed decks and porches, use treated lumber or a product the manufacturer specifically rates for exterior exposure.

What is the difference between LVL and glulam?

LVL is made from thin wood veneers. Glulam is made from full-size dimension lumber boards glued face to face. Glulam is often chosen where the beam stays exposed and appearance matters.

Can I replace an LVL beam with a steel beam?

Often, yes, and steel usually allows a shallower beam. The steel beam, its connections and the posts and footings under it must be designed by a licensed structural engineer.

Reference information only, not engineering advice. Disclaimer.